– 9 –
Carefully raise fryer to its normal position and place it in installing location.
Casters (Optional)
It is recommended that casters be installed on all batteried appliances.
If the fryer is equipped with casters the gas connector (available from Vulcan-Hart) must comply with the
Standard for Connectors of Movable Gas Appliances, ANSI-Z21.69 (latest edition), and a quick-disconnect
device that complies with the Standard for Quick-Disconnect Devices for Use With Gas Fuel, ANSI-Z21.41
(latest edition).
Provide a gas line strain relief (Fig. 1) to limit movement of the fryer without depending on the connector and/
or any quick-disconnect device or its associated piping to limit the appliance movement.
If it is necessary to disconnect the restraint, turn off the gas supply before disconnection. Reconnect the restraint
before turning the gas supply on and returning the unit to its installation position.
Instructions for installing casters to the fryer are included with the casters.
STRAIN RELIEF
FITTING FOR GAS LINE
THIS SIDE ONLY.
(Strain relief fitting
supplied by Vulcan-Hart.
Chain to be supplied by
others.)
PL-51493
Fig. 1
GAS CONNECTIONS
CAUTION: All gas supply connections and any pipe joint compound must be resistant to the action of
propane gases.
The gas inlet is located at the lower right rear. Codes require that a gas shutoff valve be installed in the gas
line ahead of the fryer.
The gas supply line must be at least the equivalent of
1
⁄2" iron pipe. If using the optional quick-disconnect flex
hose,
3
⁄4" iron pipe must be used unless
3
⁄4" to
1
⁄2" reducing fittings are used. Make sure the pipes are clean and
free of obstructions, dirt, and piping compound. A battery requires one or two connections of appropriate size
and type for the gas requirement.
WARNING: PRIOR TO LIGHTING, CHECK ALL JOINTS IN THE GAS SUPPLY LINE FOR LEAKS. USE SOAP
AND WATER SOLUTION. DO NOT USE AN OPEN FLAME.
After piping has been checked for leaks, fully purge gas pipes to remove air.
GAS PRESSURES AND ORIFICES
The standard orifices are set at 4" W.C. (Water Column) pressure for natural gas and 10" W.C. (Water Column)
pressure for propane gas. A pressure regulator is supplied as part of the gas control valve.