A gas shutoff valve is supplied with each oven and is located at the bottom of the control panel. No tools are
required to access this valve.
Connect the oven(s) to the gas line after leveling. The gas supply line must be at least the equivalent of
3
4" (19mm) iron pipe. Make sure the pipes are clean and free of obstructions, dirt and piping compound.
WARNING: PRIOR TO LIGHTING, CHECK ALL JOINTS IN THE GAS SUPPLY LINE FOR LEAKS. USE SOAP
AND WATER SOLUTION. DO NOT USE AN OPEN FLAME.
TESTING THE GAS SUPPLY SYSTEM
The oven and its individual shutoff valve must be disconnected from the gas supply piping system during any
pressure testing of that system at test pressures greater than
1
/2 psig (3.45 kPa).
The oven must be isolated from the gas supply piping system by closing the manual shutoff valve during pressure
testing of the gas supply system at test pressures equal to or less than
1
/2 psig (3.45 kPa).
GAS PRESSURES AND ORIFICES
Natural Gas
The burner orifices are sized to deliver the nameplate input rating (25,000 Btu/hr) at a gas manifold pressure of
3.5" w.c. (water column) (0.8 kPa). The gas pressure regulator is integral to the gas solenoid valve, and is factory
set to supply 3.5" w.c. (0.8 kPa) as required for natural gas.
Propane Gas
The burner orifices are sized to deliver the nameplate input rating (25,000 Btu/hr) at a gas manifold pressure of
10.0" w.c. (water column) (2.5 kPa). The gas pressure regulator is integral to the gas solenoid valve, and is
factory set to supply 10.0" w.c. (2.5 kPa) as required for propane gas.
BURNER AIR SHUTTER ADJUSTMENTS
The burner has fixed, factory adjusted air openings and requires no field adjustment.
FLUE CONNECTIONS
Ventilation requirements will vary with each installation and must comply with applicable portions of National Fire
Protection Association Standard #96 and with local codes. Considerations to be kept in mind include:
Flue connections should never be made directly to the oven.
The oven should be located under a hood which has an adequate connection to an exhaust duct and extends
six inches beyond the oven sides.
Clearance above the oven flue should be adequate for the flue products to escape so that there is no
interference with the heat circulation in the ovens. Refer to the standard for "Vapor Removal from Cooking
Equipment," NFPA #96 (latest edition).